W (ERV) Series
Rev.: 15 May, 2015
13
climatemaster.com
Mist Eliminator Filter in Intake Hood (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
3000 840 990 1065 1135 1215 1265 1335
3400 875 1060 1130 1205 1255 1320
1385
3800 1015 1120 1200 1245 1315 1365 1450
4200 1080 1195 1240 1350 1395 1445 1510
4600 1120 1200 1315 1380 1460 1515 1560
Barometric Hood, 2" Pleated Filters (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
3000 850 995 1065 1135 1220 1270 1335
3400 925 1060 1130 1225 1265 1330
1375
3800 1020 1120 1220 1285 1325 1370 1430
4200 1100 1215 1280 1345 1400 1435 1480
4600 1150 1275 1340 1415 1475 1520 1565
SUPPLY
EXHAUST
RPM Range
Low 780-1020 Standard Unit
Medium 1000-1315 Optional Kit
High 1315-1700 Optional Kit
Mist Eliminator Filter in Intake Hood (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
4600 795 900 960 1010 1090
1135 1165
5000 835 945 1000 1060 1135 1155 1230
5400 895 985 1040 1130 1155 1220 1265
5800 940 1025 1085 1145 1225 1250 1300
6200 990 1070 1105 1210 1245 1290 N/A
Barometric Hood, 2" Pleated Filters (5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
4600 780 910 900 1045 1085
1135 1185
5000 825 945 1015 1075 1125 1180 1230
5400 890 990 1065 1105 1170 1220 1270
5800 940 1025 1085 1165 1215 1250 1310
6200 980 1060 1150 1205 1235 1305 N/A
SUPPLY
EXHAUST
RPM Range
Low 700-900 Standard Unit
Medium 900-1100 Optional Kit
High 1100-1300 Optional Kit
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for WF
Blower RPM for WG